Example: If you are defining a gauge for battery voltage, you may decide that the
gauge should display between 8 and 16 volts. You may also want the range
between 11 and 13 volts to be considered normal, the range between 10 and 11
volts to be deserving of a low warning led, and any voltage below 10 volts to be
deserving of a low fault indication. You may also wish the range between 13 and
14 volts to be deserving of a high warning led, and any voltage above 14 volts to
be deserving of a high fault indication. In this case, you would set the values as
shown in the screenshot below:
Figure 27Example of setting Divisions and Ranges
9.4.10.18.16 Indicator Colors
When the parameter type is an indicator, the Colors fields allow you to enter
different colors for each of the states of the indicators. Select the desired color by
Revision 4.0.2 Page 111