Accept Re-trigger PeriodWhen you accept an alert, it will change to the
“Accepted” state, and annunciators that are sounding for that alert will stop
sounding. If the condition which caused the alert remains true after the amount of
time in this field, the alert will return to the “Active” state, and annunciators will
begin sounding again for that alert.
If a value of 0:00 is entered, then the alert will never re-trigger.
Set DelayIf the switch being monitored is in the Offstate for the amount of
time specified in this field, the alert will become active.
Clear Delay If the switch being monitored is in a state other than “Off” for the
amount of time specified in this field, the alert will become inactive.